Analog scaling and bounds in Structured Text
The Core Idea
Analog scaling translates an instrument signal into an engineering value. Range checks decide whether that value is usable; limiting a display or command is a separate choice from declaring a measurement valid.
What you will learn
Scale a 4–20 mA signal to engineering units in one assignment.
Keep the scaled value for decisions, and limit only a copy for display.
Judge whether a signal is a measurement at all, and keep a failed signal out of decisions.
Why it matters
A number that fits on a human-machine interface (HMI) is not necessarily a trustworthy measurement. The control decision must account for the signal's meaning as well as its displayed range.
The problem
A level transmitter on a tank sends 4–20 mA: 4 mA is empty, 20 mA is full. A fill pump may run while the level is below 90 %.
| Signal | Type | Meaning |
LEVEL_MA | REAL | The transmitter signal the input card measures, in mA. Starts at 12.0 mA. |
LEVEL_PCT | REAL | Scaled level, in %. |
DISPLAY_PCT | REAL | Level for the tank graphic, which can only draw 0–100 %. |
FILL_PERMIT | BOOL | TRUE lets the fill pump run. |
The program scales the signal, keeps the level inside 0–100 %, and permits the fill below 90 %. The lesson simulator scans every 100 ms.
After you lock in your prediction, type 0 into Transmitter: that is what the input card reads when a wire in the loop breaks.
See it go wrong
Try 22 mA too, a level the transmitter cannot measure. Then type 12 to put the signal back.
Fix it
Change the program so a signal below 3.8 mA or above 20.5 mA turns on SIGNAL_BAD and blocks the fill. Keep LEVEL_PCT unlimited, and limit only DISPLAY_PCT to 0–100 %. Hidden checks try signals just outside 4–20 mA that are still measurements, and a transmitter that signals its own failure. Editing pauses the program, so press Run to try your version.
Passing the checks records Structured Text progress on the shared analog-scaling concept.
What happened and why
Limiting a value replaces it. Once LEVEL_PCT was limited, a broken wire and an empty tank both read 0 %, and nothing after that line could tell them apart. The fix keeps two values with different jobs:
| Value | Limited? | Used for |
LEVEL_PCT | No | Decisions, while the signal is good; diagnosis |
DISPLAY_PCT | Yes, 0–100 % | The tank graphic only |
Whether the signal is a measurement is a question about the signal, so the program answers it in mA. This lesson uses the band from the 4–20 mA fault-handling lesson: 3.8–20.5 mA is a measurement. A healthy transmitter can read a little outside 4–20 mA when the process is just past its calibrated range. Below 3.8 mA the loop is broken or the transmitter is signalling a failure, and above 20.5 mA it is signalling a failure.
FILL_PERMIT now needs two things: a level below 90 % and a good signal. With a bad signal, the program does not know the level, so it does not permit the fill.
Common mistakes
Limiting the value that decisions use: a broken wire reads as an empty tank. Limit a display copy instead.
Flagging a bad signal without using the flag: the lamp lights, but the pump still runs. Every decision that uses the level needs
NOT SIGNAL_BAD.Judging the scaled value instead of the signal: testing
LEVEL_PCT < 0.0calls 3.9 mA a failure, although the transmitter is healthy. TestLEVEL_MAagainst the measurement band.Forgetting the 4 mA live zero:
LEVEL_MA * 100.0 / 20.0reads 60 % at 12 mA and 20 % when the tank is empty. Subtract 4 mA first, then scale the 16 mA span.Limiting only one end: at 22 mA the display tries to draw 112.5 %.
Platform notes
IEC 61131-3 (the international standard for programmable controller languages) defines
LIMIT(MN, IN, MX), which returnsINheld betweenMNandMX. Many platforms also have a scaling instruction that converts raw input counts to engineering units. This simulator has neither, so the lesson writes both withIF.Many analog input cards detect a broken wire themselves and set a status bit. Use that bit where you have it, as well as the range check.