Applied review: a small machine controller in Structured Text
The Core Idea
A machine controller combines decisions, memory, timing, and fault handling into one program that meets a written specification. The parts have to work together across scans, not just pass isolated examples.
What you will learn
Turn a written specification into a working controller: start-up, sequence, timing, counting, alarms, and recovery.
Combine the patterns from earlier lessons in one program, each in a section you can check on its own.
Test a controller the way it will be accepted: normal operation first, then injected faults.
Why it matters
A complete controller must handle ordinary operation and the transitions into and out of faults. Building from a specification gives you a way to check that whole behavior.
The specification
A conveyor carries parts past a photo-eye into a box. Write its controller in Structured Text. The lesson simulator runs the conveyor beside your program, with parts, the photo-eye, and two faults you can inject from the conveyor view: a jammed belt and a tripped motor overload.
I/O list
| Tag | Type | Direction | Meaning |
START_PB | BOOL | Input | TRUE while Start is pressed (momentary, normally open). |
STOP_PB | BOOL | Input | TRUE while Stop is not pressed (momentary, normally closed). |
RESET_PB | BOOL | Input | TRUE while the alarm Reset is pressed. |
PHOTO_EYE | BOOL | Input, from the conveyor | TRUE while a part blocks the eye. |
JAM_SENSOR | BOOL | Input, from the conveyor | TRUE while the belt is jammed. |
OVERLOAD_TRIP | BOOL | Input, from the conveyor | TRUE while the motor overload relay is tripped. |
CONVEYOR_RUN | BOOL | Output | Runs the conveyor motor. |
START_WARNING | BOOL | Output | Start-up warning horn and beacon. |
PART_COUNT | INT | Output | Parts in the current batch. |
BATCH_DONE | BOOL | Output | The batch is complete. |
JAM_ALARM, OVERLOAD_ALARM | BOOL | Output | Latched alarms. |
Sequence of operation
Start-up warning. START, with no alarm on, sounds
START_WARNINGfor 2 s with the belt stopped. Then the warning stops and the belt runs.Counting. While the belt runs, each part that passes the photo-eye adds 1 to
PART_COUNT, once per part however long it blocks the eye.Batch done. The 3rd part stops the belt and turns
BATCH_DONEon. The next START clears the count andBATCH_DONE, and starts again from step 1.Stop. Stop stops the belt, or cancels the warning, at any time. The count is kept, and START resumes from step 1.
Alarm table
| Alarm | Cause | Action | Clears when |
JAM_ALARM | JAM_SENSOR | Latches; stops the belt; blocks START | RESET is pressed and JAM_SENSOR is FALSE |
OVERLOAD_ALARM | OVERLOAD_TRIP | Latches; stops the belt; blocks START | RESET is pressed and OVERLOAD_TRIP is FALSE |
RESET only clears alarms. It never starts the belt.
Acceptance tests
The visible tests are a start-up, a full batch with a restart, and a jam with its recovery. Hidden tests stop and resume mid-batch, trip the overload and try to start during it, and press Stop during the warning. Each time in a test has one scan of tolerance either side.
Build it
The skeleton declares a step number, the warning timer, and an edge detector, and marks five sections. Fill them in one at a time, pressing Run after each, and operate the human-machine interface (HMI) as you go. When normal operation works, use Field faults under the program to jam the belt and trip the overload, and check every row of the alarm table. Then press Run checks. The simulator scans every 100 ms.
Passing every acceptance test records Structured Text progress on the applied review.
How the parts fit
Each requirement maps to a pattern you have already written:
| Requirement | Pattern | From |
| Alarms latch, clear on RESET only once the cause is gone | Fault latch: set on the cause, ELSIF reset | Start/stop memory, Hysteresis and alarm memory |
| One count per part | Rising edge, R_TRIG | Edges and event counting |
| 2 s warning | TON called on every scan, with IN := STATE = 10 | Timers and elapsed time |
| Idle, warning, running, batch done | CASE that only changes the step; outputs from the step | CASE and machine sequencing |
| Stop and alarms win | The clearing IF after the sequence | Start/stop memory |
Keeping each requirement in its own section is what makes a controller reviewable: someone checking the alarm table reads section 1, not the whole program.
Common mistakes
Counting every scan the eye is blocked: one part adds 3 or 4. Count the rising edge.
Letting Reset clear an alarm whose cause is still there: the alarm drops while the belt is still jammed. Test the cause before RESET, in one
IF/ELSIF.Checking Stop and the alarms before the sequence: the
CASEruns after them and can start the warning while an alarm is on. Put them after theCASE.Calling the warning timer inside its step: the timer never resets, so the next start's warning lasts one scan.
Platform notes
A real start-up warning is set by the site's safety assessment: its length, and whether it must sound before every start. Treat the 2 s here as an example value.
Many sites write a specification like this one as a functional design specification (FDS), and run its tests as a factory or site acceptance test (FAT or SAT) with the customer present.